9424200892 Rev F 25
Setting Range
Dataset List selectable
Data Tags List selectable
Mapped To
IED Name List selectable
LDevice Inst List selectable
Logical Node List selectable
FC CO
DO Name List selectable
DA Name Oper.ctlVal
Report Controls
The Report Controls tab is illustrated in Figure 21.
Figure 21. Report Controls Tab
Reporting is handled by the REPORT-CONTROL-BLOCK class of the ACSI. This class controls the
procedures that are required for reporting values of DATA from one or more LNs to one client.
Three trigger options (data-change, quality-change, and data-update) can cause a report to be sent to a
client. Report control is divided into two classes: BUFFERED-REPORTCONTROLBLOCK (abbreviated
BRCB) and UNBUFFERED-REPORT-CONTROLBLOCK abbreviated (URCB).