Vista de pagina 83
78 9424200774 Rev B
Register Table BE1-11
Name
Description
Group
Register
Type
Bytes
Writable
Unit
Range
Style
50-5
Mode
SG1
21440
4180*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-5
Source
SG1
21442
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-5
Pickup
SG1
21444
4182*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-5
Time Delay
SG1
21446
4184*
Float
4
R W
Millisecond
0 - 60000
FGIMT
50-5
Direction
SG1
21448
4186*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-5
Mode
SG2
21450
4188*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-5
Source
SG2
21452
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-5
Pickup
SG2
21454
4190*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-5
Time Delay
SG2
21456
4192*
Float
4
R W
Millisecond
0 - 60000
FGIMT
50-5
Direction
SG2
21458
4194*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-5
Mode
SG3
21460
4196*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Unbalance=9
FGIMT
50-5
Source
SG3
21462
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-5
Pickup
SG3
21464
4198*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-5
Time Delay
SG3
21466
4200*
Float
4
R W
Millisecond
0 - 60000
FGIMT
50-5
Direction
SG3
21468
4202*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
50-6
Mode
SG0
21470
4204*
Uint32
4
R W
n/a
Disabled=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
FGIMT
50-6
Source
SG0
21472
Uint32
4
R W
n/a
CT1=0
CT2=1
FGIMT
50-6
Pickup
SG0
21474
4206*
Float
4
R W
Amp
0.5 - 150
FGIMT
50-6
Time Delay
SG0
21476
4208*
Float
4
R W
Millisecond
0 - 60000
FGIMT
50-6
Direction
SG0
21478
4210*
Uint32
4
R W
n/a
Forward=0
Reverse=1
Non-Directional=2
FGIT
Vista de pagina 83