9424200994 Rev N 133
Figure 84. Distance Settings Screen
Table 49. Operational Settings
Setting Range Increment
Unit of
Measure
Default
Select Delta/Wye
Compensation
None, DAB (+30), or DAC (30) n/a n/a Disabled
Mode
Disabled or Enabled
n/a
n/a
Disabled
Diameter
0 to 500
varies
ohms
0
Time Delay
0 to 300,000
varies
milliseconds
0
Torque Angle
0 to 90
1
degrees
45
Offset
500 to 500
varies
ohms
0
BE1-11g Distance (21) Protection