3-6 BE1-700 Modbus Protocol 9376700991 Rev D
40039 Report Selection SI
Read: Returns the current value of Report Selection.
Writing to Report Selection terminates previous report and initializes new report. See the
table for values.
40040 Report Focus INT
Read: Returns the current value of Report Focus.
Write: See Table 3-1 for values.
Note: If an illegal Report Focus value is written, the user is not notified until a read of the
Report Text is attempted.
Note: Write to Report Selection and Report Focus to specify the report which will be
made available via the Report (RPT) Template. The template is the Report Text Block at
47595-719.
Table 3-1. Report
Report Text
47595-719
Report Selection
40039
Report Focus
40040
RA-LGC Report 0 Not used
RA-MAJ Report 1 Not used
RA-MIN Report 2 Not used
RA-REL Report 3 Not used
RF Report 4 Not used
RF-# Report 5 Value of # (1 255)
RF-NEW Report 6 Not used
RS Report 7 Not used
RS-# Report 8 Value of # (1 - 255)
RS-NEW Report 9 Not used
RS-F# Report 10 Value of # (1 255)
RS-ALM 11 Not used
RS-IO 12 Not used
RS-LGC 13 Not used
Global Parameters
Global Parameter registers 40080 - 40099 are effective only for serial communication ports active with
ASCII protocol and for the Modbus serial port, COM2, when Password Security register 40989 is enabled.
40080-83 Global Password ASC(8)
40085-88 Setting Password ASC(8)
40090-93 Control Password ASC(8)
40095-98 Report Password ASC(8)
Read: If global access granted, password ASCII strings are read. Otherwise, the ASCII string of
'*' characters is read.
Write: Password in ASCII string.
Note: If password written is less than 8 characters long, a binary zero value must be
included following the final password character.
40084 Global Path BM(8)
40089 Setting Path BM(8)
40094 Control Path BM(8)
40099 Report Path BM(8)
Read: Path associated with password
Write: Path associated with password
Bit 2 is set for COM 2 access.
Bit 1 is set for COM1 access.
Bit 0 is set for COM0 / FP access.