9376700991 Rev D BE1-700 Modbus Protocol 3-9
Read: To read a value other than ASCII character 'X', the Select Output register must be the most
recent control register written AND must have been written within the previous 30
seconds.
P if Pulse Output selection has been made.
0 if Latch Output at 0 selection has been made.
1 if Latch Output at 1 selection has been made.
L if programmable Logic selection has been made.
E if Enable All Outputs serial control has been made.
D if Disable All Outputs serial control has been made.
X if Output control not selected or control timer has expired.
Write: The desired ASCII character.
P to select Pulsing Output.
0 to select Latching Output at 0.
1 to select Latching Output at 1.
L to select programmable Logic.
E to select Enabling All Outputs override control.
D to select Disabling All Outputs override control.
40140 Operate Output A ASC(1)
40142 Operate Output 1 ASC(1)
40144 Operate Output 2 ASC(1)
40146 Operate Output 3 ASC(1)
40148 Operate Output 4 ASC(1)
40150 Operate Output 5 ASC(1)
Read: Current control.
P to Pulse Output.
0 to Latch Output at 0.
1 to Latch Output at 1.
L to select programmable Logic.
D if All Outputs override control Disabled
Write: The desired ASCII character to alter control (corresponding Select register must contain
same value, written within previous 30 seconds).
P to Pulse Output.
0 to Latch Output at 0.
1 to Latch Output at 1.
L to select programmable Logic.
E to Enable All Outputs override control.
D to Disable All Outputs override control.
Requires an additional write of 'Y' to Exit register 40001 to allow these control settings to be saved to
the relay internal EEPROM.
Group Setting Parameters
40259-60 50TP Pickup FP
40264-65 50TN Pickup FP
40269-70 50TQ Pickup FP
40274-75 150TP Pickup FP
40279-80 150TN Pickup FP
40284-85 150TQ Pickup FP
Read and Write: 0.50 to 150.00 amps
40261-62 50TP Time Delay LI
40266-67 50TN Time Delay LI
40271-72 50TQ Time Delay LI
40276-77 150TP Time Delay LI
40281-82 150TN Time Delay LI
40286-87 150TQ Time Delay LI
Read and Write: 0 to 60,000 milliseconds