3-14 BE1-700 Modbus Protocol 9376700991 Rev D
2 - 1200 Baud (Do not select for Port 2 Modbus communications)
3 - 2400 Baud
4 - 4800 Baud
5 - 9600 Baud
6 - 19K Baud
40981 Serial Port 2 Relay Address INT
Read and Write: 0 to 65,534
40964 Serial Port 0 Software Flow Control SI
Read: 0 if XON / XOFF Control is disabled, 1 if XON / XOFF Control is enabled
Write: 0 to disable XON / XOFF Control, 1 to 255 to enable XON / XOFF Control
40965 Serial Port 0 Page Length SI
Read and Write: 0 for disabled, 1 to 40 for number of lines / page
40966 Serial Port 0 Acknowledgement Format SI
Read: 0 if No acknowledge, 1 if Acknowledge enabled
Write: 0 for No acknowledge, 1 to 255 to enable acknowledge
40986 Serial Port 2 Modbus Parity SI
Read and Write: 0 for No parity, 1 for Even parity, 2 for Odd parity
40987 Serial Port 2 Modbus Remote Delay SI
Read and Write: 1 to 20: 10 to 200 milliseconds
40988 Serial Port 2 Modbus Stop Bits SI
Read and Write: 1 for One stop bit, 2 for Two stop bits
40989 Password Security SI
Read and Write: Default value is disabled, 1 to enable Password Security.
When Password Security is enabled, relay parameters can be changed via Modbus only
if access is obtained via the Access Password and Access Request holding registers and
released via the Exit register with value 89 (ASCII character 'Y').
0 to disable Password Security.
When Password Security is disabled, no access is required (Access Password, Access
Request, and Exit holding registers have no effect) and no password protection is used.
Global Parameters, holding registers 40080 - 40099 (ASCII command GS-PW) have no
effect on the Modbus serial port, COM2.
System Data Setting Parameters
41018 System Frequency SI
Read and Write: 50 for 50 hertz, 60 for 60 hertz
41019-20 Phase Rotation ASC(3)
Read and Write: ABC for ABC rotation, ACB for ACB rotation
41021 Phase CT Ratio INT
41022 Ground CT Ratio INT
Read and Write: 1 to 50,000
41033-34 Phase VT Ratio FP
41041-42 Auxiliary VT Ratio FP
Read and Write: 1.00 to 10000
41035-36 27/59 Voltage Sensing Mode ASC(3)
41037-38 51/27R Voltage Sensing Mode ASC(3)
Read and Write: PP for Line, PN for Phase