Vista de pagina 13
OBJECT
REQUEST
(BE1-851E will parse)
RESPONSE
(BE1-851E will respond with)
Object
No.
Variation
No.
Description
Function
Codes (dec)
Qualifier Codes
(hex)
Function
Codes (hex)
Qualifier Codes
(hex)
30 4 16-Bit Analog Input Without
Flag
1 (read)
06 (no range)
07,08 (limited qty)
81 00,01 (start-stop)
17,28 (index)
32 0 Analog Change Event
(Variation 0 is used to request
default variation)
1 (read)
07,08 (limited qty)
32 1
(default -
see note 1)
32-Bit Analog Input without
time
1 (read)
07,08 (limited qty)
81 17,28 (index)
32 2 16-Bit Analog Input without
time
1 (read)
07,08 (limited qty)
81 17,28 (index)
32 3 32-Bit Analog Input with time 1 (read)
81 17,28 (index)
32 4 16-Bit Analog Input with time 1 (read)
81 17,28 (index)
40 0 Analog Output Status -
(Variation 0 is used to request
default variation)
1
06 (no range)
07,08 (limited qty)
40 1
32-bit Analog Output Status 1 (read)
06 (no range)
07,08 (limited qty)
81 00,01 (start-stop)
17,28 (index)
40 2
(default -
see note 1)
16-bit Analog Output Status 1 (read)
06 (no range)
07,08 (limited qty)
81 00,01 (start-stop)
17,28 (index)
41 1 32-bit Analog Output Block 3 (select)
4 (operate)
5 (direct op)
6 (dir op noack)
07,08 (limited qty)
17,28 (index)
81 echo of request
41 2 16-bit Analog Output Block 3 (select)
4 (operate)
5 (direct op)
6 (dir op noack)
07,08 (limited qty)
17,28 (index)
81 echo of request
50 1 Time and Date 1 (read)
2 (write)
06 (no range or all)
07 (limited qty=1)
08 (limited qty)
81 00,01 (start-stop)
17,28 (index)
60 1 Class 0 Data (Note 1) (Note 4)
1 (read)
81
60 2 Class 1 Data 1 (read)
81
60 3 Class 2 Data 1 (read)
81
60 4 Class 3 Data 1 (read)
81
80 1 Internal Indications 2 (write)
102 1 8-Bit Unsigned Integer (Note
2)
1 (read)
06 (no range)
07,08 (limited qty)
81(response) 00,01 (start-stop)
17,28 (index)
No Object(function code only)
(See Note 3)
13 (cold restart)
No Object(function code only)
(See Note 3)
14 (warm
restart)
No Object (function code only)
23 (delay meas)