Basler-electric BE1-851E DNP3 Protocol Manual de usuario Pagina 27

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 40
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 26
Point
Index
Description
Complementary
(C) or
Single (S)
Function Index
Permitted Codes
9
Hardware Output A Local
Control
S
0x03(Latch On/NUL) or
0x41(PulseOn/Close) sets output to
relay logic
10
Hardware Output 1 Local
Control
11
Hardware Output 2 Local
Control
12
Hardware Output 3 Local
Control
13
Hardware Output 4 Local
Control
14
Hardware Output 5 Local
Control
15
Hardware Output 6 Local
Control
16
Hardware Output 7 Local
Control
17
All Hardware Outputs’ Local
Control
18
43 Selector Switch Status -
Latch control
C
0x03(Latch On/NUL) or
0x41(PulseOn/Close) sets Selector
Switch to 1
0x04 (Latch Off/NUL) or
0x81(PulseOn/Trip) sets Selector Switch
to 0
19
143 Selector Switch Status -
Latch control
20
243 Selector Switch Status -
Latch control
21
343 Selector Switch Status -
Latch control
22
Setting Group 0
S
0x03(Latch On/NUL) or
0x41(PulseOn/Close) selects group
to be active
23
Setting Group 1
24
Setting Group 2
25
Setting Group 3
26
Local Setting Group Control
Switch S
0x03(Latch On/NUL) or
0x41(PulseOn/Close) returns Setting
Group Control to relay local logic
27
101 Virtual Breaker Control
Switch
C
0x41(PulseOn/Close) Close breaker
0x81(PulseOn/Trip) Trip breaker
28
Hardware Output A - Pulse
Control
S
0x81(Pulse On/Trip) or
0x01(Pulse On/NUL)
Pulse output / Selector switch to opposite
of current state then restore
to previous state(pulsed output is active
200 to 250 ms)
29
Hardware Output 1 - Pulse
Control
30
Hardware Output 2 -Pulse
Control
31
Hardware Output 3 -Pulse
Control
32
Hardware Output 4 -Pulse
Control
9289900792 Rev C BE1-851E DNP Protocol 5-7
Vista de pagina 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 39 40

Comentarios a estos manuales

Sin comentarios