Point
Index
Description
Change Event
Assigned
Class (1,2,3 or
none)
Notes
26
79 Sequence Control Block
1
27
Input Contact 1
1
28
Input Contact 2
1
29
Input Contact 3
1
30
Input Contact 4
1
31
101 Trip
1
32
101 Close
1
33
101 Slip Contact ( 0= Breaker Tripped, 1 = Breaker Is Closed )
1
34
Logic Alarm
1
35
Major Alarm
1
36
Minor Alarm
1
37
Output Trip Coil Monitor
1
38
Setting Group 0 Active
1
39
Setting Group 1 Active
1
40
Setting Group 2 Active
1
41
Setting Group 3 Active
1
Hardware Output Status (points 42 - 49)
42
Output A
1
43
Output 1
1
44
Output 2
1
45
Output 3
1
46
Output 4
1
47
Output 5
1
48
Output 6
1
49
Output 7
1
Programmable Alarms (points 50 - 75) See Note 2
50
Trip Circuit Monitor Alarm
1
51
Breaker Fail Alarm
1
52
Recloser Fail Alarm
1
53
Recloser Lockout
1
54
Breaker Alarm 1
1
55
Breaker Alarm 2
1
56
Breaker Alarm 3
1
57
P Demand Alarm
1
58
N Demand Alarm
1
59
Q Demand Alarm
1
60
Group Override (0=Local Control, 1= Group Override)
1
61
Sys I/O Delay Alarm
1
62
Communication Error Alarm
1
5-2 BE1-851E DNP Protocol 9289900792 Rev C